Permit Case Summary

Case Number: Search Help

Case Number:SEP2005-00377 Case Status:Canceled Date Received:11/4/2005
Description:NOW FILED WITH SEP09-159 lots 22 & 33 Date Issued:3/9/2006
Applicant:WILLIAM PAQUIN Expiration Date:3/9/2009 12:00:00 AM
Site Address:251 ANN KIVLEY DR Case Finaled:
Parcel No:972000022 Other Cases Parcel Data Map It More Details

Case Actions
Below is a list of actions that have been taken by staff for this permit case. They are sorted based on the date they were added to the database with most recent actions at the top. A value in the "Date Completed" field indicates that the action has been completed.
Description: Miscellaneous inspection
Date Completed: 3/3/2010
Disposition: DONE
Description: Cancel/withdraw application
Date Completed: 5/14/2009
Disposition: DONE
Description: Issue permit (F)
Date Completed: 3/9/2006
Disposition: DONE
Description: Pending letter; add inf (F)
Date Completed: 3/9/2006
Disposition: DONE
Description: Print ESA Review Form-F
Date Completed: 11/4/2005
Disposition:
Description: Septic Permit Application (F)
Date Completed: 11/4/2005
Disposition: DONE
Description: Case Entered
Date Completed: 11/4/2005
Disposition:
Description: Stormwater Review-U
Date Completed: 12/22/2005
Disposition: DONE
Description: Env. Sensitive Area Review-U
Date Completed: 12/22/2005
Disposition: DONE
Description: Initial Site Inspection by HD
Date Completed: 11/28/2005
Disposition: DONE
Description: Pressure test required
Date Completed:
Disposition:

Case Conditions
Below is a list of conditions for this permit case. Conditions typically record requirements that the applicant must meet to be in compliance with the permit.
Title: pud monitoring
Wording H - AS PER WAC 246-272 AND JEFFERSON COUNTY CODE 8.15 ALL SYSTEMS REQUIRE MONITORING. THIS MONITORING IS PROVIDED BY AGREEMENT BETWEEN THE JEFFERSON COUNTY ENVIRONMENTAL HEALTH DIVISION AND THE JEFFERSON COUNTY PUBLIC UTILITY DISTRICT #1. THIS SEWAGE DISPOSAL SYSTEM WILL REQUIRE AN ACTIVE MONITORING CONTRACT WITH THE PUD #1 PRIOR TO FINAL APPROVAL OF THE SEWAGE DISPOSAL SYSTEM. While the County strongly recommends that the property owner allow inspectors to enter their property to inspect the system in order to insure that the system is functioning correctly, the property owner always has the right under the Fourth Amendment and our State Constitution, to refuse the inspectors access to their property. The property owner never loses the right to refuse access and can do so despite never having refused access before.

Title: pressure test observation
Wording Health Dept. required to observe pressure test when system fully installed/complete, 48 hours notice to be provided for scheduling.

Title: alternative-asbuilt required
Wording H - An asbuilt drawing and certification of completion by the designer is required prior to final approval.

Title: curtain drain
Wording Curtain Drain required a minimum of 10' upgradient of primary and reserve drainfields.

Title: well setback requirement
Wording Setbacks to all wells- 100' required from drainfield and reserve areas. 50' required from tanks and effluent transport lines.

Title: dry season installation
Wording Dry season installation required.

Title: protection from vehicular traffic
Wording A 30' area downslope of the Glendon and reserve area shall be protected from all parking, driving and other land disturbing activities. All components of the septic system are to be completely protected from vehicular traffic or mechanical disturbance.

Title: installed on natural contours
Wording Drainlines are to be installed along the natural contours.

Title: dose counter
Wording Dose counters are required in the control panel for all drainfield components.

Title: divert drainage
Wording Divert all sources of drainage, including roof drains away from septic tank and drainfield area.

Title: water tight tank
Wording Septic tank and pump chamber to be water tight. Extra protection (i.e. Bentonite) to be used around inlet, outlet, and risers due to high water table.

Title: no building permit guarantee
Wording Approval/issuance of a sewage disposal permit does not guarantee the approval of other development or a building permit on this site. Compliance with other Jefferson County and Washington State Codes is required.

Title: UDC compliance
Wording Approval of this sewage disposal permit does not preclude the permit holder from complying with the Unified Development Code for other/future development on the site.

Title: minimum land RESTRICTIVE COV
Wording H - This permit is granted based on the recorded RESTRICTIVE COVENANT combining lots 22 & 33 of Melwood Terrace to meet the minimum land area required under WAC 246-272 Onsite Sewage Code. COVENANT recorded 1/24/06, #507745

Title: risers
Wording Risers are required to grade with secured lids over both compartments and over the outlet of the septic tank for inspection and maintenance/monitoring. Minimum 20" riser over inlet.

Title: MONITORING SCHEDULE
Wording As per Jefferson County Code 8.15 all onsite sewage systems require monitoring. Monitoring shall be provided by an approved entity. THIS SYSTEM IS REQUIRED TO BE INSPECTED EVERY 3 YEARS....AT 6 MONTHS, AT ONE YEAR AND .....EVERY 3 YEARS...ANNUALLY THEREAFTER.

Title: Water line setback
Wording 10' separation required between a Water line and all portions of the onsite sewage system; effluent transport line, tanks, treatment and disposal components.

Title: Setback - Drains
Wording A 30' setback shall be maintained from the disposal component and reserve area to any downslope footing, curtain or interceptor drain or drainage ditch.

Title: O & M Manual required
Wording Before final approval is given, the designer shall provide an operations and maintenance manual to the property owner. The manual must instruct the owner of the on site sewage system on the ways to properly operate and maintain all components of the system.

Title: Designer Notification/inspections
Wording Designer must be contacted prior to start of construction and for inspections during installation.

Title: Stormwater BMPs
Wording The project shall adhere to the Best Management Practices (BMPs) to control stormwater, erosion and sediment during construction. BMPs shall address permanent measures to stabilize soil exposed during construction, and in the design and operation of stormwater and drainage control systems.


Case Findings
Below is a list of findings for this permit case. Findings typically record facts that the staff are using as the basis of their permit processing decisions.
Title: F-Confirmed ESAs
Wording The application was reviewed by the Jefferson County staff for the potential presence of Environmentally Sensitive Areas (ESAs) under the provisions of the Unified Development Code (UDC). After an initial Geographic Information Systems mapping review and an investigative site inspection, the following ESAs were confirmed to be present on the subject property: Wildlife Habitat.