Permit Case Summary

Case Number: Search Help

Case Number:SEP1999-00099 Case Status:Finaled Date Received:4/20/1999
Description: Date Issued:5/25/1999
Applicant:SARA BROWN Expiration Date:5/25/2000 12:00:00 AM
Site Address:200 CURTISS ST Case Finaled:1/24/2000
Parcel No:989400110 Other Cases Parcel Data Map It More Details Parcels Images

Case Actions
Below is a list of actions that have been taken by staff for this permit case. They are sorted based on the date they were added to the database with most recent actions at the top. A value in the "Date Completed" field indicates that the action has been completed.
Description: OSS Inspection-5 Year
Date Completed: 12/29/2004
Disposition: DONE
Description: OSS Inspection-3 Year
Date Completed: 12/20/2002
Disposition: DONE
Description: SEPTIC PERMIT FINALED "F"
Date Completed: 1/24/2000
Disposition: DONE
Description: Issue permit (F)
Date Completed: 5/25/1999
Disposition: ISS
Description: Case Entered
Date Completed: 4/20/1999
Disposition:
Description: Review Case
Date Completed: 5/25/1999
Disposition: ISS
Description: PUD contract required
Date Completed: 8/23/1999
Disposition:
Description: AsBuilt from engineer req
Date Completed: 1/21/2000
Disposition: DONE
Description: Pressure test required
Date Completed: 7/23/1999
Disposition: DONE
Description: Septic Permit Application (F)
Date Completed: 4/22/1999
Disposition:

Case Conditions
Below is a list of conditions for this permit case. Conditions typically record requirements that the applicant must meet to be in compliance with the permit.
Title: pud monitoring
Wording AS PER WAC 246-272 ALL ALTERNATIVE SYSTEMS REQUIRE MONITORING. THIS MONITORING IS PROVIDED BY AGREEMENT BETWEEN THE JEFFERSON COUNTY ENVIRONMENTAL HEALTH DIVISION AND THE JEFFERSON COUNTY PUBLIC UTILITY DISTRICT #1. THIS SEWAGE DISPOSAL SYSTEM WILL REQUIRE AN ACTIVE MONITORING CONTRACT WITH THE PUD #1 PRIOR TO FINAL APPROVAL OF THE SEWAGE DISPOSAL SYSTEM.

Title: pressure test observation
Wording Health Dept. required to observe pressure test, 48 hour notice to be given.

Title: well setback requirement
Wording Setbacks to all wells- 100' required from drainfield and reserve areas. 50' required from tanks and effluent transport lines.

Title: protection from vehicular traffic
Wording All components of the septic system are to be completely protected from vehicular traffic or mechanical disturbance. Protective barriers are required around drainfield.

Title: dose counter
Wording Dose counters are required in the control panel for all drainfield components.

Title: divert drainage
Wording Divert all sources of drainage, including roof drains away from septic tank and drainfield area.

Title: transport line double cased
Wording Any portion of transport line under a driven way is to be double cased or equivalent.

Title: water tight tank
Wording Asphaultic emulsion or equivalent required on septic tank and/or pump chamber.

Title: no building permit guarantee
Wording Approval/issuance of a sewage disposal permit does not guarantee the approval of other development or a building permit on this site. Compliance with other Jefferson County and Washington State Codes is required.

Title: SAND LINED TRENCH/BED
Wording BED TO BE EXCAVATED TO 46" DEPTH AND THEN BACKFILLED WITH ASTM 33 TYPE SAND TO 24" AND UP SIDE WALLS AS PER DESIGN.

Title: critical area compliance
Wording Approval of this sewage disposal permit does not preclude the permit holder from complying with the Critical Areas Ordinance for other development on the site.

Title: CUSTOM CONDITION
Wording Existing tank shall be pumped and properly abandoned prior to final approval of system.